Consequence Assessments of a Cold BLEVE. Can We Do It Better?

Résumé

Presently in France the control authority (DREAL) in charge of the inspection of the Seveso installations requires the examination of the scenario "cold BLEVE" of very flammable liquid storages (flash point < 273K; vapour pressure > 10 5 Pa at 308K). The proposed case study reports the consequence analysis of a 4,800 m 3 spherical isopentane storage tank. The potential cold BLEVE is characterized by a ground level cloud fire associated with a weak fireball tangential to the ground level. Estimations of the explosion energy, blast overpressure and thermal radiation effects were examined with different models. Uncertainties are carefully studied. The prescribed calculation methodology constitutes a basis for administrative decision with important consequences for the safety of population, industry and Land Use Planning.
Fichier principal
Vignette du fichier
CET, 2016, v48, 211-216 ala.pdf (882.08 Ko) Télécharger le fichier
Origine : Fichiers éditeurs autorisés sur une archive ouverte
Loading...

Dates et versions

hal-01926270 , version 1 (28-11-2018)

Identifiants

Citer

André Laurent, Laurent Perrin, Olivier Dufaud. Consequence Assessments of a Cold BLEVE. Can We Do It Better?. Chemical Engineering Transactions, 2016, Proceedings of the 15th International Symposium on Loss Prevention and Safety Promotion in the Process Industrie, June 05-08, Freiburg (Germany), 48, pp.211-216. ⟨10.3303/CET1648036⟩. ⟨hal-01926270⟩
112 Consultations
227 Téléchargements

Altmetric

Partager

Gmail Facebook X LinkedIn More