A New Control Scheme of Hybrid Active Filter Using Self-Tuning-Filter - Université de Lorraine Access content directly
Conference Papers Year :

A New Control Scheme of Hybrid Active Filter Using Self-Tuning-Filter

Abstract

This paper presents a new control scheme using Self Tuning Filter placed in both feedback and feedforward control of a parallel hybrid active filter. This hybrid active filter is intended for harmonic compensation of a diode rectifier. The use of self tuning filters simplifies the control scheme by reducing the number of extraction filters, used in classical feedback and feedforward loop. More, in this case, no Phase Locked Loop is necessary for the feedforward loop. The studied hybrid active filter consists of an active filter and three phase tuned LC filters for 7 th harmonic frequency. The non linear load is a diode rectifier feeding a (R, C) parallel load. The effectiveness of the new proposed scheme has been verified by computer simulation and the results are compared with the classical control scheme.

Domains

Electric power
Not file

Dates and versions

hal-03565842 , version 1 (11-02-2022)

Identifiers

Cite

Mohamed Abdusalam, Philippe Poure, Shahrokh Saadate. A New Control Scheme of Hybrid Active Filter Using Self-Tuning-Filter. 2007 International Conference on Power Engineering, Energy and Electrical Drives, Apr 2007, Setubal, Portugal. pp.35-40, ⟨10.1109/POWERENG.2007.4380095⟩. ⟨hal-03565842⟩